The Quest 506 removes 500 pints per day at 80°F and 60 percent RH and 320 pints at 75°F and 50 percent, on about 10 amps at 230 volts. Used units are either the R410A model 4036600 or the current R454B model 4046300. That line on the data plate decides the controls you need and who can service it.

What are the Quest 506 specs?

The current Quest 506 208/230V, model 4046300, is a 2,250 watt unit rated at 500 pints per day and 9.2 pints per kWh at 80°F and 60 percent. These figures come from Quest's Quest 506 208/230V spec page.

  • Capacity: 500 pints per day at 80°F and 60 percent, 320 pints per day at 75°F and 50 percent.
  • Efficiency: 9.2 pints per kWh at 80°F and 60 percent, 6.8 pints per kWh at 75°F and 50 percent.
  • Electrical: 208 to 230 volts single phase, 9.9 amps at 230 volts, 10.9 amps at 208 volts, 6 ft 12/3 cord with a NEMA 6-20P plug.
  • Airflow: 1,150 CFM at zero static.
  • Size and weight: 44.8 by 29.0 by 27.4 inches, 275 lb.
  • Refrigerant: R454B, 3 lb 14 oz charge.
  • Heat to the room: 30,500 BTU per hour total, of which 22,800 is heat of condensation and 7,700 is motor load.
  • Filter and drain: MERV 13 filters, 18 by 20 by 2 inches, and a 3/4 inch threaded NPT drain that needs a P trap.
  • Controls: onboard digital controls with a low voltage terminal block for remote control.
  • Operating window: 56°F to 95°F.
  • Listings and warranty: UL rated, ETL listed, California Title 24 compliant, 5 year limited warranty.

Quest also builds a 277 volt version, model 4046310, with the same capacity and airflow at 8.2 amps on a NEMA L7-20P cord. Both mount freestanding or overhead on 3/8 inch threaded rod.

How is the old R410A Quest 506 different from the new one?

The old Quest 506, model 4036600, pulls slightly more water at flower setpoints but uses more power and has no onboard humidistat. Quest's discontinued Quest 506 page says the line was redesigned with a more environmentally conscious refrigerant and points buyers to the two current models.

  • Capacity at 80°F and 60 percent: old 506 pints, new 500 pints.
  • Capacity at 75°F and 50 percent: old 349 pints, new 320 pints.
  • Efficiency at 75°F and 50 percent: old 6.2 pints per kWh, new 6.8.
  • Power and current: old 2,700 watts and 11 amps, new 2,250 watts and 9.9 amps at 230 volts.
  • Airflow: old 1,500 CFM, new 1,150 CFM.
  • Voltage: old 220 to 240 volts, new 208 to 230 volts.
  • Refrigerant: old R410A, 4 lb 8 oz. New R454B, 3 lb 14 oz.
  • Controls: old unit requires an external control. New unit has onboard controls.
  • Weight: old 280 lb, new 275 lb.

On paper the old unit removes 29 more pints a day at 75°F and 50 percent. It also draws about 450 more watts, which shows up twice: once on the meter and again as cooling load. The higher airflow helps throw dry air across a wide room, which is the one place we'd give the old unit an edge.

Should you buy an R410A dehumidifier in 2026?

An R410A dehumidifier is still a working machine, but you should price it as one with a narrower service path than the R454B model that replaced it. Any sealed system repair on the old unit means a technician working in R410A, matched to the 4 lb 8 oz charge Quest lists for it.

Before you buy an old 506, confirm that your HVAC contractor services R410A equipment and will stock it. A sealed system leak in week 6 of flower is a bad time to learn they won't. If the unit is going into a new build where you will run it for years, the current model is usually the better buy.

The old unit also has a voltage catch. The Quest 506 installation manual says model 4036600 needs a buck boost transformer to run on 208 volts or 277 volts. Many commercial buildings serve 208 volts, so check the panel before the unit ships.

How many Quest 506 units does a flower room need?

A Quest 506 handles about 40 gallons a day of transpired water at 75°F and 50 percent, since 320 pints is 40 gallons. A room irrigating 100 gallons a day with 10 percent runoff puts roughly 90 gallons into the air, so it needs three units at that setpoint, plus a fourth as a spare.

Those four units add 122,000 BTU per hour of heat, a little over 10 tons, and each wants its own 20 amp circuit. That load has to be in the cooling design before equipment is ordered. Our guide to cannabis HVAC design shows where dehumidifier heat lands in the tonnage calculation.

If your room sits between models, the Quest dehumidifier sizing guide covers the 335 and 746 with the same method. For the case against residential style units, see grow optimized versus industrial dehumidifiers.

What should you check on a used Quest 506?

Check the data plate, the warranty status, the controls and the coil, then run the unit for an hour and confirm it makes water. Most of what goes wrong with a used Quest 506 shows up in that hour. Here is our order on inspection day:

  1. Read the data plate. Record the part number (4036600, 4036610, 4046300 or 4046310), refrigerant, voltage and serial number.
  2. Assume no warranty. The 506 manual limits coverage to the original end user and states it is not transferable. Years 2 to 5 covered only the condenser, evaporator and compressor, with labor paid by the owner.
  3. Find out how it was controlled. The old 506 has no humidistat. It takes a 24 VAC signal on terminals R, C, DHUM, FAN and FLOAT from a Quest DEH3000R or another 24 volt dehumidify signal. If the seller keeps the controller, budget one. Leave the FLOAT jumper in place unless you wire a normally closed float switch.
  4. Pull the filters. The 506 takes two MERV 13 filters, 18 by 20 by 2 inches. The manual says running without them can clog the coil badly enough to require disassembly. A missing filter on a used unit is a reason to look hard at the coil face.
  5. Run the field test. With field wiring disconnected, jumper 24 volts to FAN and confirm only the fan runs. Then jumper to DEHU and confirm the compressor starts after a short delay. Run it an hour in air above a 50°F dew point and look for water at the drain.
  6. Clamp the amps. Compare running current to the plate: 11 amps on the old 506, 9.9 amps at 230 volts on the new one. A compressor that cycles while the fan runs can mean defrost cycling in cold air, a dirty filter or a failed overload.
  7. Check for frost. A continuously frosted evaporator points to low charge, a bad defrost sensor, a dirty filter or restrictive ducting.
  8. Look at the hang points. The manual calls for four 3/8 inch rods from the threaded nut retainers, no longer than 6 ft, and a drain pan where a leak could damage what is below.

A used dehumidifier that passes this list is a good buy for a room that needs capacity now. Our new versus used equipment guide covers when the savings justify the risk. Humidity control is also the front line on mold; our microbial mitigation service audits rooms where dehumidification is falling behind.

Quest 506 FAQ

Does the Quest 506 need a humidistat?

The current Quest 506 (4046300 and 4046310) has onboard digital controls and also accepts a remote signal through its low voltage terminal block. The discontinued 4036600 has no built in humidistat and needs an external 24 VAC dehumidify signal, such as a Quest DEH3000R, to run. Check which one you are buying before you plan the controls.

What plug does the Quest 506 use?

The current 208/230V Quest 506 ships with a 6 ft cord and a NEMA 6-20P plug, and the 277 volt version ships with a NEMA L7-20P cord. The older 4036600 used a NEMA 6-20P on a 10 ft cord. The 506 manual says not to run the unit on an extension cord and recommends a GFI protected circuit.

Can an old Quest 506 run on 208 volts?

Not directly. The 506 manual says model 4036600 is a 220 to 240 volt unit that needs a buck boost transformer to run on 208 volts or 277 volts. The current 4046300 is rated for 208 to 230 volts, and the 4046310 runs on 277 volts, so either current model avoids the transformer.

What filter does the Quest 506 take?

Every Quest 506 version takes MERV 13 pleated filters sized 18 by 20 by 2 inches, and the 506 manual lists a quantity of two. The manual calls for checking filters every six months and changing them at least every grow cycle. In a dusty room or one with heavy trim traffic, we would check them monthly.